Preset Frequencies - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

P3.3.8 KEYPAD REFERENCE COPY (ID 181)
You can use this parameter to set the selection of copy settings when you go from Remote to Local (keypad)
control.
P3.3.9 FIELDBUS CONTROL REFERENCE SELECTION (ID 122)
You can use this parameter to select the reference source when the control place is Fieldbus.
10.3.2

Preset Frequencies

You can use the Preset frequencies function in processes where more than one fixed frequency reference is
necessary. Eight preset frequency references are available. You can select a preset frequency reference using the
digital input signals P3.5.1.16, P3.5.1.17, and P3.5.1.18.
P3.3.10 PRESET FREQUENCY MODE (ID 182)
You can use this parameter to set the logic of the digital input preset frequencies. With this parameter, you can set
the logic which one of the preset frequencies is selected into use. There is a selection of two different logics.
Selection number Selection name
0
Binary coded
1
Number (of inputs used)
P3.3.11 PRESET FREQUENCY 0 (ID 180)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
P3.3.12 PRESET FREQUENCY 1 (ID 105)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
P3.3.13 PRESET FREQUENCY 2 (ID 106)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
P3.3.14 PRESET FREQUENCY 3 (ID 126)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
P3.3.15 PRESET FREQUENCY 4 (ID 127)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
P3.3.16 PRESET FREQUENCY 5 (ID 128)
You can use this parameter to set the preset frequency reference when the preset frequencies function is used.
Select the preset frequencies with the digital input signals.
CODING METHOD OF PRESET FREQUENCIES
Description
The mix of the inputs is binary coded. The different sets of active
digital inputs determine the preset frequency. See more data in Table
66. SELECTING PRESET FREQUENCIES WHEN P3.3.10 = Binary
coded.
Number (of inputs used) The number of active inputs tells which
preset frequency is used: 1, 2, or 3.
101
HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719