Group 3.8: Limit Supervisions - Honeywell HVAC400x Applications Manual

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

5.8

Group 3.8: Limit Supervisions

Index
Parameter
Supervision #1 Item
P3.8.1
Selection
P3.8.2
Supervision #1 Mode
P3.8.3
Supervision #1 Limit
Supervision #1 Limit
P3.8.4
Hysteresis
Supervision #2 Item
P3.8.5
Selection
P3.8.6
Supervision #2 Mode
P3.8.7
Supervision #2 Limit
Supervision #2 Limit
P3.8.8
Hysteresis
Table 25. Limits supervision settings
Min
Max
Unit
0
7
0
2
Varies
Varies
Varies
Varies
Varies
Varies
0
7
0
2
Varies
Varies
Varies
Varies
Varies
Varies
55
HVAC400X – APPLICATION MANUAL
Default
ID
Description
0 = Output frequency.
1 = Frequency reference.
2 = Motor current.
3 = Motor torque.
0
1431
4 = Motor power.
5 = DC-link voltage.
6 = Analog input 1.
7 = Analog input 2.
0 = Not used.
1 = Low limit supervision (output active
0
1432
under limit).
2 = High limit supervision (output
active over limit).
25.00
1433
5.00
1434
1
1435
See P3.8.1.
0
1436
See P3.8.2.
40.00
1437
See P3.8.3.
5.00
1438
See P3.8.4.
EN2B-0417GE51 R0719