HVAC400X – APPLICATION MANUAL
Selection number Selection name
24
Reserved
25
PID1 supervision limits
26
PID2 supervision limits
27
Motor 1 control
28
Motor 2 control
29
Motor 3 control
30
Motor 4 control
31
Motor 5 control
32
Reserved
33
Reserved
34
Maintenance warning
35
Maintenance fault
36
Thermistor Fault
37
Motor switch
38
PreHeat
39
kWh Pulse Output
40
Run Indication
41
Selected Param.Set
P3.5.3.2.2 RO1 ON DELAY (ID 11002)
You can use this parameter to set the ON delay for the relay output.
P3.5.3.2.3 RO1 OFF DELAY (ID 11003)
You can use this parameter to set the OFF delay for the relay output.
EN2B-0417GE51 R0719
continued: The output signals through RO1
Description
The feedback value of PID1 controller is not in the supervision limits.
The feedback value of PID2 controller is not in the supervision limits.
The contactor control for the Multi-pump function.
The contactor control for the Multi-pump function.
The contactor control for the Multi-pump function.
The contactor control for the Multi-pump function.
The contactor control for the Multi-pump function.
(Always OPEN.)
(Always OPEN.)
WARNING: Time elapsed maintenance must be scheduled.
Alarm: Time elapsed maintenance must be performed.
A thermistor fault occurred.
The Motor Switch function has detected that the switch between the
drive and the motor is open.
The selected active parameter will trigger the relay.