Honeywell HVAC400x Applications Manual page 166

Variable frequency drives for variable torque applications
Table of Contents

Advertisement

HVAC400X – APPLICATION MANUAL
Fault code Fault ID
Fault name
65
1065
PC communication fault
66
1066
Thermistor fault
Maintenance counter 1
1301
alarm
Maintenance counter 1
1302
fault
Maintenance counter 2
1303
alarm
68
Maintenance counter 2
1304
fault
Maintenance counter 3
1305
alarm
Maintenance counter 3
1306
fault
1310
1311
69
Fieldbus mapping error
1312
Process supervision fault
101
1101
(PID1)
Process supervision fault
105
1105
(PID2)
110
1110
Speed lowered
Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative:
Home and Building Technologies
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 01
Fax
+49 (0) 7031 637 740
http://ecc.emea.honeywell.com
EN2B-0417GE51 R0719
continued: Fault codes
Possible cause
The data connection between the
PC and the drive is defective.
The motor temperature is too
high.
Maintenance counter has
reached the alarm limit.
Maintenance counter has
reached the fault limit.
Maintenance counter has
reached the alarm limit.
Maintenance counter has
reached the fault limit.
Maintenance counter has
reached the alarm limit.
Maintenance counter has
reached the fault limit.
The ID number that is used to
map the values to Fieldbus
Process Data Out is not valid.
It is not possible to convert one
or more values for Fieldbus
Process Data Out.
There is an overflow when the
values for Fieldbus Process Data
Out (16-bit) are mapped and
converted.
The PID controller: The feedback
value is not in the supervision
limits and the delay, if you set the
delay.
The PID controller: The feedback
value is not in the supervision
limits and the delay, if you set the
delay.
The drive lowers the current limit
to protect itself from overheating.
This decreases also the output
frequency.
Subject to change without notice
Remedy
Check the motor cooling and the load.
Check the thermistor connection.
If the thermistor input is not used, you
have to short-circuit it.
Carry out the needed maintenance and
reset the counter.
Check the parameters in the Fieldbus
Data Mapping menu
The type of the value is undefined.
Check the parameters in the Fieldbus
Data Mapping menu.
 