Prohibited Frequencies (Control Panel: Menu Par  P10) - Honeywell HVAC232 Series Applications Manual

Table of Contents

Advertisement

Aux cw data in selection
Parameter defines the input process data coupled to Aux Control Word.
0 =
Not used
1 =
PDI1
2 =
PDI2
3 =
PDI3
4 =
PDI4
5 =
PDI5
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
10.10 Prohibited Frequencies
(Control panel: Menu PAR
Prohibit frequency range 1: Low limit
Prohibit frequency range 1: High limit
Prohibit frequency range 2: Low limit
Prohibit frequency range 2: High limit
Two skip frequency regions are available if there is a need to avoid certain
frequencies because of e.g. mechanical resonance. In this case the actual
frequency reference sent to the motor control will be kept out of these rang-
es according to the example below, where one range is in use.
Actual Reference
High Lim
Low Lim
Low
Lim
Fig. 58. Frequency Range
P10)
High
Requested Reference
Lim
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents