Appendix C. Timers - Pyronix Enforcer 32-WE Programming And Installation Manual

Wireless alarm system
Hide thumbs Also See for Enforcer 32-WE:
Table of Contents

Advertisement

A p p e n d i x C .
Timer
Function
Entry Time
Entry time for each area. (if programmed as the input type 'Final Exit')
Exit Time
Exit time for each area.
Siren Time
Cut off time for external sounder. Separate for each area.
Confirm Time
Time period during which a second activation must occur to qualify as
'sequentially confirmed' alarm. NOTE: BS8243 specifies a confirm
time between 30 and 60 minutes. This also can be used in
conjunction with testing an omit signal.
HU Confirm
Time period during which a second activation on a hold alarm must
Time
occur to qualify as 'sequentially confirmed' alarm. NOTE: BS8243
specifies a confirm time between 8 and 20 hours. This also can be
used in conjunction with testing an omit signal.
Strobe Time
Time strobe output remains live after siren time ends.
'99' means endless.
Re-Arm No.
Number of times system re-arms after bell time ends.
NOTE: Re-arm number applies to each area, and does not affect
emergency alarms. '9' means always re-arm.
AC Signal
Time delay before mains failure or technical alarm notified. NOTE:
Delay
Setting '250' = never alarms. System change-over to battery
supply
immediate.
Some ATE imposes a randomised delay in notifying a mains fail. This
should be taken into account when setting this timer.
Settle
Time between final exit input closing, and system setting.
Double Knock
Length of filter period applied to inputs with 'Double Knock' attribute.
Pre-Alarm
Delays 'Intruder' output signals if entry time has started. Pre-alarm
time must be set for at least 30 seconds to comply with PD6662
Line Fault
Duration of Telecom Line Fault before 'Line Fault' alarm triggered.
NOTE: In the case of devices connected via the ATE pins, this time is
additional to that already applied by the ATE.
Set Fail
Time after which 'Set Fail' operation will be invoked if exit procedure
not completed.
Fire Siren
Cut off time for fire alarm. '99' means endless.
Time
Set Fail
Time for which a set fail warning will be present.
Warning
Wireless
This option is only applicable if wireless devices are installed. It is the
Supervision
time window before a wireless supervision fault will be signalled. For
Time
example: if the time is set for 2 hours, then any device that doesn't
communicate with the wireless expander within that period will cause a
supervision fault. This must be programmed to 2 hours or less for
compliance to EN50131.
Wireless
This option is only applicable if wireless devices are installed. It is the
Jamming
time window that if a wireless device had its signal 'blocked' a fault
Time
would display. For example, if the time is set to 30 seconds, then if a
wireless device is 'jammed' longer than 30 seconds a fault will be
displayed. This must be programmed to 30 seconds or less (but not
zero) for compliance to EN50131.
Service Time
This is a timer that can be set in days, and will display a message to
the user warning that a service is due. An engineer code will clear the
message.
Enforcer Programming Manual
T i m e r s
and
associated
visual
alert
indication
Page: 50
Range
0 – 255 seconds
0 – 255 seconds
2 – 15 minutes
1 – 99 minutes
8 – 20 hours
0 – 99 minutes
0 – 9
is
always
0 – 250 minutes
0 - 255 seconds
0 – 75 seconds
0 – 255 seconds
0 – 250 seconds
0 – 255 seconds
1 – 99 minutes
0 – 99 seconds
0-99 hours
0-100 seconds
367 days

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents