NOTE:
1
1. *
means that the Administrator password is needed. For password
information, please refer to 7.5 Password Entry.
2
2. *
means that the Alarm Threshold Values (High & Low)*
the service personnel during the installation process of the optional battery
management system (BMS).
3
3. *
means that the item will only show up after you select 'Main' in the Module
list.
UPS-1.1
MEASUREMENT
BMS SETTING
Module
Module Address
Main
Alarm Threshold Setting Values
Cell Voltage (V)
String Voltage (V)
Ambient Temperature (°C)
Item
Module
Set the module as Main/ Ext #n.
Module Address
Set the module address.
Module Type
Set the module type as Voltage Type/ internal Resistance.
The status 'Enable/ Disable' determines whether or not the LCD
Status
shows the BMS information of the optional battery management
system (BMS).
SETUP
MAINTENANCE
BMS Setting
String ID
1
1
Internal Resistance
High
15.0
576.0
70.0
7-59
7
4
LOG IN
WARNING
Administrator
Module Type
Status
Enable
Low
10.5
368.0
25.0
Description
LCD Display & Settings
2
are defined by
10:15
Sep 25,2018
On-Line