6.2.8 Energy Recycle Mode Start-up Procedures

1
Ensure that the Manual Bypass Breaker (Q3), Output Breaker (Q4) and every external
battery cabinet's breaker (Q5) are in the OFF position.
2
Switch ON the Input Breaker (Q1) and Bypass Breaker (Q2).
3
After you switch on the Input Breaker (Q1) and Bypass Breaker (Q2), each auxiliary
power card's LED indicator will illuminate green and the following status will occur
simultaneously.
(1) The system and each power module will start initialization. After each power
For the locations of the parallel communication card, auxiliary power cards, power
modules and associated LED indicators, please refer to Figure 6-1.
4
The LCD initial screen (see Figure 6-39) will appear within 40 seconds after the Input
Breaker (Q1) and Bypass Breaker (Q2) are turned on.
Modulon DPH Series
WARNING:
Energy Recycle mode is only applicable to single input and single unit application.
the card will start initialization. After initialization, the parallel communication
card's LED indicator will illuminate green.
NOTE:
If you purchase an additional parallel communication card (optional) and
install it in the parallel communication card slot shown in Figure 4-12,
initialization. After initialization, the parallel communication card's LED
indicator will illuminate yellow. For more information, please refer to 4.1.7
Parallel Communication Card.
(Figure 6-39: LCD Initial Screen)
6-30