Main Menu - Delta Modulon DPH Series User Manual

Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

7
System Status
The screen above indicates that the UPS is in Frequency Conversion mode and the
bypass output is restricted. For Frequency Conversion mode settings, please refer to
7.10.2 Mode Setting and 6.2.6 Frequency Conversion Mode Start-up Procedures.
8
System Status
After the Manual Bypass Breaker (Q3) is turned on, the UPS will be switched to Manual
Bypass mode and the screen above will appear. Before maintenance, the UPS must be
switched to this mode and it must be ensured that all input power, bypass power and battery
not be protected. If there is any sudden malfunction in the bypass, the loads will lose power.
Please refer to 6.2.4 Manual Bypass Mode Start-up Procedures.
7.7

Main Menu

There are three main menu icons
Modulon DPH Series
UPS-1.1
MEASUREMENT
SETUP
Power Flow
POWER FLOW
Maintenance
Power Flow
Bypass
Bypass
Summary
Mains
90 %
5 mins
EMS
UPS-1.1
MEASUREMENT
SETUP
Power Flow
POWER FLOW
Maintenance
Power Flow
Bypass
Bypass
Summary
Mains
90 %
5 mins
EMS
MAINTENANCE
LOG IN
EVENT LOG
Administrator
MAINTENANCE
LOG IN
WARNING
Administrator
,
and
MEASUREMENT
SETUP
MAINTENANCE
7-16
10:15
May 25,2018
Frequency
Conversion
Load
30 %
10:15
2
May 25,2018
Bypass
Load
30 %
, and their positions are shown

Advertisement