Additional system components
9.1 Terminal Module TM54F
LED
Color
Single digital inputs, not fail-safe
DI x
Green
Fail-safe digital outputs with associated readback channel
F_DO y
Green
(0+..3+,
0-..3-)
Readback input DI 2y for output F_DO y (y = 0..3) at test stop.
The status of the LEDs also depends on the type of external circuit.
DI 2y
Green
Cause and rectification of faults
The following reference contains information about the cause of faults and how they can be
rectified:
SINAMICS S120 Combi List Manual
190
Status
Off
No signal at digital input x (x = 20..23)
Continuous
Signal at digital input x
light
Continuous
Output y (y=0 .. 3) carries a signal
light
Off
One of the two output lines y+ or y- or both lines of output y
carry a signal
Continuous
Both output lines y+ and y- carry no signal
light
Description, cause