Replacing The Fan On The Control Supply Module - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

13.3.3

Replacing the fan on the Control Supply Module

Replacement fan (order number: 6SL3160-0AB00-0AA0)
NOTICE
When replacing the fan, you must observe the ESD regulations.
Only qualified personnel are permitted to install spare parts!
Risk of electric shock
The power supply (400 V AC) must be switched off before replacing a fan.
A hazardous voltage is present for up to 5 minutes after the supply has been switched off.
Before removing the component, check that the system is in a no-voltage condition.
Table 13- 4
Removing the fan
1. Switch off the power supplies (3-ph. 400 V AC for Control Supply Module and S120 Combi)
2. Remove the component from the drive line-up.
3. Open the device cover (6 TX10 screws)
1. Unlatch and pull out the plug connector
2. Release the 2 Torx screws (TX20)
SINAMICS S120 Combi
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0
DANGER
3. Remove the fan
Service and maintenance
13.3 Replacing the fan
283