Output Test - YSI MultiDO 5400 User Manual

Monitor, control, & alarm instruments
Table of Contents

Advertisement

2.
Press
to select.
3.
When prompted, "Are you sure?", select one of the following to confirm,
4.
Press
to save configuration and return to Run Screen.

Output Test

Menus → System → Service→Output Test
Use the Output Test menu to verify that local relays and remote device relays and
IOEM 4/20mA output channels, are wired and communicating correctly over the
network. Entering this menu turns off any active relays and disables any sensor, aux,
and timer system relays from energizing regardless of value or condition. Systems are
not reset when the Output Test menu is exited. To reset systems after exiting the Relay
Test menu power cycle the 5X00 whose output channel was tested. See note below.
Note:
-
Timer and control icon(s) remain at the Run Screen until the system is reset.
Example - the timer icon remains at systemwide location until the end of the
timer cycle that was stopped when the output test menu was entered even
though the relay is not energized. To reset systems after exiting the Relay Test
menu, power cycle the 5X00.
Directions to test outputs
1.
Enter Output Test menu
Menus → System → Service→Output Test>Output Test infor-
mation warning window is displayed
2.
at Run Screen to proceed with Output Test. Output Test Menu
opens:
Configuring the 5X00
YSI 5X00
144
3.
at Instrument menu. Device Address menu opens. Scroll and select
networked instrument whose relay or channel is to be tested.
Note:
-
If local machine is selected, configured instrument name, if configured, is
displayed after selection. See notes regarding local versus remote instrument
and relay names in 5X00 menus - page 136.
4.
at Channel. Channel menu opens. Scroll and select channel/relay
to be tested.
Notes:
-
Channel names are always listed as generic channels 1-8 regardless if local
machine is selected and the selected relay name has been user configured.
Channel 1-8 are always listed regardless if instrument selected is a 5200A or
an REM which instruments have 4 relay channels, and not 8 relay channels