Errors of additional equipment: CM2K
Sensor reg. 1. circuit
E29-1
Sensor reg. 2. circuit
E29-2
Sensor reg. 3. circuit
E29-3
Sensor reg. 4. circuit
E29-4
Sensor reg. 5. circuit
E29-5
Sensor reg. 6. circuit
E29-6
Sensor reg. 7. circuit
E29-7
Sensor reg. 8. circuit
E29-8
Corrector reg. 1. circuit
E30-1
Corrector reg. 2. circuit
E30-2
Corrector reg. 3. circuit
E30-3
Corrector reg. 4. circuit
E30-4
Corrector reg. 5. circuit
E30-5
Corrector reg. 6. circuit
E30-6
Corrector reg. 7. circuit
E30-7
Corrector reg. 8. circuit
E30-8
Errors of additional equipment: Pelet suction system
The flap is not closed
E31
There are no pellets in the
E32
big tank/room
The Mole or Feeder
E33
screw does not work
Communication error with
E34
the CMVAC
Technical instructions REGULATION PelTec / PelTec-lambda
Boiler status: Boiler work normally. The problem occurs in
the work of additional equipment CM2K if embedded.
Boiler status: Boiler work normally. The problem occurs in
the work of additional equipment - "pellet suction system" if
installed.
Possible causes: Check if the flap is blocked with pellets , if
the sensor is soiled with dust, if the sensor is about 1 mm
distant from the flap, if the sensor reacts on the flap ( the LED
lamp is switching on the sensor ).
Boiler status: Boiler work normally. The problem occurs in
the work of additional equipment - "pellet suction system" if
installed.
Possible causes: Check the pellet level in the big
tank/room , check if the flexible tubes are blocked, check
if the turbine net is full with dust.
Boiler status: Boiler work normally. The problem occurs in
the work of additional equipment - "pellet suction system" if
installed.
Possible causes: Check the electric connections on the
mole/feeder screw, check the filthiness of the mole/feeder
screw
Boiler status: Boiler work normally. The problem occurs in
the work of additional equipment - "pellet suction system" if
installed.
Possible causes:Check the UTP cable and its connections
with the electric boards.