2. TEMPERATURE (CONFIGURATION BUF)
2.1 / 2.3 BUFFER TANK TEMP.
Possible selection:
default:
80°C
Minimum:
40°C
Maximum: 85°C
The possibility of setting the desired temperature of the accumulation tank.
2.2 / 2.4 MIN. BUF. TANK TEMP.
Possible selection:
default:
20°C
Minimum:
5°C
Maximum: 64°C
The possibility of setting the minimum temperature of the accumulation tank. When minimum temperature of
accumulation tank (upper sensor) is reached, all heat pumps connected to the boiler control will be shut down.
The minimum accumulation tank temperature does not affect the operation of the DHW pump.
2.3 / 2.5 DIFF. BUF. TANK TEMP.
Possible selection:
default:
10°C
Minimum:
5°C
Maximum: 30°C
The possibility of setting the accumulation tank start difference.
2.4 / 2.6 DIFF. STOP BUF. TANK
Possible selection:
default:
5°C
Minimum:
3°C
Maximum: 30°C
The possibility of setting the accumulation tank stop difference.
2.1 MAX. BOILER TEMP. (ONLY 69/96)
Possible selection:
default:
85°C
Minimum:
80°C
Maximum:
90°C
The possibility of setting maximum boiler temperature.
Technical instructions REGULATION PelTec / PelTec-lambda
12-48
Temperatures (BUF)
69/96
17