Centrometal PelTec Series Technical Instructions page 50

Table of Contents

Advertisement

History
4.0. HISTORY
Error list / warnings used in order to have an insight into the errors / warnings that have occurred.
Written is: time of occurrence errors / warnings, error code / warning; description of the error /
warning. The first press on the field error / warning field error / warnings is indicated, in addition to see
and date generated errors / warnings.The second press on the selected error / warning, prints a
detailed description of the error / warnings and corrective action errors / warnings.
E - conditions that result the shutdown of the boiler. The error must be rectified before the next boiler
starts.
ERROR
DHW sensor error
E1
Buffer tank sensor error
E2
(Up)
Buffer tank sensor error
E3
(Down)
Flue gas sensor error
E4
Outside temperature
E5
sensor error
Main flow sensor error
E6
Return flow sensor error
E7
Pellet supply tube
temperature too high
E8
50
NAME
Boiler status: Boiler go to phases S7, C0 and OFF.
Possible causes:Interruption on el. connections between
sensor and boiler, connection to the boiler, cold
connection or DHW sensor is invalid.
Boiler status: Boiler go to phases S7, C0 and OFF.
Possible causes: Interruption on el. connections between
sensor and boiler, cold connection or buffer tank sensor (up)
is invalid.
Boiler status: Boiler go to phases S7, C0 and OFF.
Possible causes: Interruption on el. connections between
sensor and boiler, cold connection or buffer tank sensor
(down) is invalid.
Boiler status: Boiler go to phases S7, C0 and OFF.
Possible causes: Interruption on el. connections between
sensor and boiler, cold connection or invalid flue gas
sensor.
Boiler status: Boiler work normally, problem appears on
work of CM2K regulator if is installed.
Possible causes: Interruption on el. connections between
sensor and boiler, cold connection or invalid outside
temperature sensor.
Possible causes: Interruption on el. connections between
sensor and boiler, cold connection or invalid main flow
sensor.
Boiler status: Boiler go to phases S7, C0 and OFF.
Possible causes: Interruption on el. connections between
sensor and boiler, connection to the boiler, cold connection
or invalid return flow sensor.
Boiler status: Staying in phase OFF (can be appear in OFF
phase because of bimetal sensor information about too high
temperature).
Possible causes:Feeding tube temperature is higher than
80°C, interruption on el. connections between bimetal
sensor and boiler, connection to boiler, cold connection or
invalid bimetal sensor.
Technical instructions REGULATION PelTec / PelTec-lambda