Centrometal PelTec Series Technical Instructions page 35

Table of Contents

Advertisement

TEMPERATURE (KONFIGURACIJA AKU--IKG)
2. TEMPERATURE (CONFIGURATION HYDRAULIC CROSSOVER)
NOTE:
in this configuration PelTec-lambda 69/96 boiler works only with CM2K module which must
be installed and configurated
69/96
2.1 CROSSOVER TEMP. (ONLY 12-48)
Possible selection:
default: 80°C / Minimum: 70°C / Maximum: 85°C
The possibility of setting the hydraulic crossover temperature.
2.1 MAX. BOILER TEMP. (ONLY 69/96)
Possible selection:
default: 75°C / Minimum: 75°C / Maximum: 80°C
The possibility of setting maximum boiler temperature.
2.2 DIFF. BOILER (ONLY 69/96)
Possible selection:
default: 8°C
The view of boiler difference setting (not possible to change).
2.3 MIN. Tcro (ONLY 69/96)
Possible selection:
default: 70°C / Minimum: 40°C / Maximum: 70°C
The possibility of setting minimum crossover temperature.
2.3 MIN. Tcro (DHW) (ONLY 69/96)
Possible selection:
The view of set temperature of the minimum crossover temperature for DHW (always is set the same as
DHW temperature).
Technical instructions REGULATION PelTec / PelTec-lambda
12-48
IMPORTANT:
default view of the menu
when CM2K is not
installed and configurated
BOILER CAN'T WORK!
Temperatures (CRO)
69/96
35