Diagnostics Alarms - Siemens SIMATIC ET 200SP Manual

Digital output module dq 4x24vdc/2a hs 6es7132-6bd20-0da0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

6.3.3

Diagnostics alarms

Diagnostics alarms
A diagnostics alarm is output and the DIAG LED flashes on the module for each diagnostics
event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the
CPU. You can evaluate the error codes with the user program.
Note
You can connect 2 actuators per output.
The diagnostics of the two actuators influence each other in the case of duplicate wiring.
This means that a single short-circuit affects both actuators.
Table 6- 11
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarms
Error code
Short circuit
1
1 2
H
Excess temperature
5
H
Parameter assign-
10
ment error
No supply
11
voltage
Communication
13
error
Error 1 in actua-
1D
tor/sensor
Error 2 in actua-
1E
tor/sensor
Channel temporarily
1F
not available
The channels 0 and 1 or 2 and 3 each form a load group. Within a load group, a short-circuit can have an effect on the
1
adjacent channel. The load groups do not have an effect on each other in the case of a short-circuit.
If the short-circuit persists, the module heats up. This may trigger temperature monitoring with excess temperature
2
diagnostic interrupt.
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC
Meaning
Short-circuit of the actuator supply
The module has detected that the maxi-
mum permitted module temperature has
been exceeded. All channels of the mod-
ule are switched to high resistance. The
module is then restarted.
The module cannot evaluate parame-
H
ters for the channel.
Incorrect parameter assignment.
No or insufficient supply voltage L+
H
Module is defective.
H
The encoder data is invalid.
H
The encoder module is removed or not
H
ready to operate
Firmware update is currently in progress
H
or was canceled.
The module does not output any process
values or substitute values in this state.
Cam control operating mode
6.3 Interrupts/diagnostics alarms
Solution
Correct the process wiring
Correct the process wiring
Correct the parameter assignment
Check supply voltage L+ on the Ba-
seUnit
Check BaseUnit type
Replace the module.
Check encoder module and connect-
ed sensor.
Check messages about encoder
modules and eliminate any errors.
Insert encoder module
Insert server module
Check connection to the controller
Wait for firmware update.
Restart the firmware update.
89