PWR LED
Table 3- 5
3.3.2

Interrupts

The DQ 4×24VDC/2A HS digital output module supports diagnostic interrupts.
Diagnostic interrupts
The module generates a diagnostic interrupt at the following events:
● Short circuit
● Excess temperature
● Parameter assignment error
● No supply voltage
● Communication error
● Channel temporarily not available
Detailed information on the event is available in the STEP 7 online help.
3.3.3

Diagnostics alarms

Diagnostics alarms
A diagnostics alarm is output and the DIAG LED flashes on the module for each diagnostics
event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the
CPU. You can evaluate the error codes with the user program.
Note
You can connect 2 actuators per output.
The diagnostics of the two actuators influence each other in the case of duplicate wiring.
This means that a single short-circuit affects both actuators.
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC
Status display of the PWR LED
PWR LED
Meaning
No supply voltage L+
Off
Supply voltage L+ present
On
DQ operating mode DQ (valve control)
3.3 Interrupts/diagnostics alarms