Siemens SIMATIC ET 200SP Manual page 31

Digital output module dq 4x24vdc/2a hs 6es7132-6bd20-0da0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

DQ operating mode DQ (valve control)
3.3 Interrupts/diagnostics alarms
Table 3- 6
Diagnostics alarms, their meaning and corrective measures
Diagnostics alarms
Error code
Short circuit
1
1 2
H
Excess temperature
5
H
Parameter assign-
10
ment error
No supply
11
voltage
Communication
13
error
Channel temporarily
1F
not available
The channels 0 and 1 or 2 and 3 each form a load group. Within a load group, a short-circuit can have an effect on the
1
adjacent channel. The load groups do not have an effect on each other in the case of a short-circuit.
If the short-circuit persists, the module heats up. This may trigger temperature monitoring with excess temperature
2
diagnostic interrupt.
30
Meaning
Short-circuit of the actuator supply
The module has detected that the maxi-
mum permitted module temperature has
been exceeded. All channels of the mod-
ule are switched to high resistance. The
module is then restarted.
The module cannot evaluate parame-
H
ters for the channel.
Incorrect parameter assignment.
No or insufficient supply voltage L+
H
Module is defective.
H
Firmware update is currently in progress
H
or was canceled.
The module does not output any process
values or substitute values in this state.
Solution
Correct the process wiring
Correct the process wiring
Correct the parameter assignment
Check supply voltage L+ on the Ba-
seUnit
Check BaseUnit type
Replace the module.
Wait for firmware update.
Restart the firmware update.
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC

Advertisement

Table of Contents
loading

Table of Contents