A.3 Parameter assignment and structure of the parameter data record for pulse width modulation operating mode
Error code in the
STATUS parameter (hexadeci-
mal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
E0
02
H
H
H
DF
80
E1
01
H
H
H
DF
80
E1
02
H
H
H
DF
80
E1
06
H
H
H
DF
80
E1
0A
H
H
H
DF
80
E1
0D
H
H
H
DF
80
E1
21
H
H
H
DF
80
E1
24
H
H
H
See also
Parameter assignment and structure of the parameter data record for pulse width modulation
operating mode (Page 110)
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC
Meaning
Error in the header, length or number of
H
parameter blocks
Reserved bit set
H
Invalid diagnostics enable bit set for oper-
H
ating mode
Code for behavior with substitute value
H
invalid
Value for substitute value invalid
H
Code for output rate invalid
H
Set operating mode invalid
H
Code for pulse width modulation time peri-
H
od invalid
Parameter data records
Solution
Correct the length and number of parame-
ter blocks, see Figure A-14 Header infor-
mation (Page 111) and Figure A-17
Channel header information (Page 112).
Write 0 to all reserved bits.
Correct the diagnostics enables according
to the operating mode, see Figure A-16
Module parameter block (Page 112).
Use valid code for reaction to CPU STOP,
see Figure A-18 Structure of byte x to x+7
for channels 0 to 3 (Page 113).
Adapt substitute value to valid value, see
Figure A-18 Structure of byte x to x+7 for
channels 0 to 3 (Page 113).
Use valid code for output rate, see Figure
A-16 Module parameter block (Page 112).
Adapt operating mode according to the
configuration, see Figure A-16 Module
parameter block (Page 112).
Use valid code for pulse width modulation
time period, see Figure A-18 Structure of
byte x to x+7 for channels 0 to 3
(Page 113).