Pulse width modulation operating mode

5.2 Parameters/address space

5.2
Parameters/address space
5.2.1

Pulse width modulation

Function
In the "pulse width modulation" operating mode, the four outputs only provide a pulse width
modulated output signal.
The digital channel is activated with a pulse duty cycle that is updated cyclically as a function
of the output value from the user program. The actuating signal is output digitally as a pulse
train of on and off pulses.
Figure 5-3
Configuration
You configure the pulse width modulation with the following parameters:
● "Pulse width modulation" operating mode
● Pulse width modulation time period
● Substitute value duty cycle
46
Time period T; frequency of the pulse width modulation: f = 1/T
Pulse duration (duty factor)
Pulse width modulation
Digital output module DQ 4x24VDC/2A HS (6ES7132-6BD20-0DA0)
Manual, 06/2018, A5E32855695-AC