FIBER METER
Fiber Meter CABLE CERTIFICATION REPORT #3
Circuit ID: TX2
Cable Test Standard: 568A
Backbone Link
Location:
Date Tested: 11/21/2000
Test Mode: Two-Way
TEST SUMMARY: PASS
Number of Connections: 2
Number of Splices: 0
Core Diameter: 62.5
Length: PASS
Measured Length
322 ft
Optical Loss: PASS
Direction
Wavelength
850 nm
1300 nm
Direction
Wavelength
850 nm
1300 nm
Operator: _______________________
Comments:
Figure 7-5. Sample two-way Autotest report.
78
Module Type: MultiMode
Remote Module Type: MultiMode
Serial Number: 9904401 V1.00D0
Cable IOR: 1.490
Limit
Delay
6560 ft
488 ns
Main->Remote
Loss dB
Limit dB
0.45 dB
1.87 dB
0.47 dB
1.65 dB
Remote->Main
Loss dB
Limit dB
0.89 dB
1.87 dB
0.33 dB
1.65 dB
Margin dB Status
1.42 dB
PASS
1.18 dB
PASS
Margin dB Status
0.98 dB
PASS
1.32 dB
PASS
Date: ____________________
END REPORT #3