Monitoring The Insulation Resistance; Undervoltage/Overvoltage Monitoring - Bender ISOMETER isoEV425 Manual

Insulation monitoring device for unearthed dc circuits (it systems) for the charging of electric vehicles
Table of Contents

Advertisement

If the values R
or U
F
hysteresis) for the period t
back to their initial position and the alarm LEDs "AL1"/"AL2" stop lighting. If
the fault memory is activated, the alarm relays remain in alarm condition and
the LEDs light until the reset button "R" is pressed or the supply voltage U
interrupted.
The device function can be tested using the test button "T". Parameters are as-
signed to the device via the LCD and the control buttons on the front panel;
this function can be password-protected. Parameterisation is also possible via
the BMS bus, for example by using the BMS Ethernet gateway (COM465IP) or
the Modbus RTU.
3.2.1

Monitoring the insulation resistance

The two parameters that monitor the insulation resistance, R1 and R2, can be
found in the response value menu "AL" (see table in
can only be set higher than the value R2. If the insulation resistance R
or falls below the activated values R1 or R2, an alarm message will be sig-
nalled. If R
exceeds the values R1 or R2 plus the hysteresis value (see table in
F
Chapter
5.3.1), the alarm will be cleared.
3.2.2

Undervoltage/overvoltage monitoring

In the response value menu "AL" (see
("U <" and "U >") for monitoring the mains voltage can be activated or deacti-
vated. The maximum undervoltage value is limited by the overvoltage value.
The r.m.s. value of the nominal system voltage U
system voltage U
"U >"), an alarm will be signalled. If the maximum permissible nominal system
voltage U
set for the ISOMETER® is exceeded, an alarm message will be initi-
n
ated even when the overvoltage limit value has been deactivated. The alarm
will be deleted when the limit values plus hysteresis (see
longer violated.
16
do not violate their release value (response value plus
n
without interruption, the alarm relays will switch
off
reaches, falls below or exceeds the limit values ("U <" or
n
Chapter
Chapter
5.3), the parameters
is monitored. If the nominal
n
isoEV425_D00126_09_M_XXEN/03.2019
Function
5.3). The value R1
reaches
F
Chapter
5.3.1) are no
is
s

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISOMETER isoEV425 and is the answer not in the manual?

This manual is also suitable for:

Isometer isoev425hcAgh420

Table of Contents