Functional Description - Bender ISOMETER isoEV425 Manual

Insulation monitoring device for unearthed dc circuits (it systems) for the charging of electric vehicles
Table of Contents

Advertisement

Function

3.2 Functional description

The ISOMETER® measures the insulation resistance R
capacitance C
between the system to be monitored (L1/+, L2/-) and earth
e
(PE). The RMS value of the nominal system voltage U
as well as the residual voltages U
tween L2/- and earth) are also measured.
From a minimum value of the nominal system voltage, the ISOMETER® deter-
mines the faulty conductor L1/+/L2/-, which shows the distribution of the in-
sulation resistance between conductors L1/+ and L2/-. The distribution is
indicated by a positive or negative sign preceding the insulation resistance
measurement. The value range of the faulty conductor is ±100 %:
The partial resistances can be calculated from the total insulation resistance R
and the faulty conductor (R %) using the following formula:
Fault at conductor L1/+ R
Fault at conductor L2/-
Also from a minimum value of the nominal system voltage, the ISOMETER® de-
termines the insulation resistance R
U
. It is an approximate value for one-sided insulation faults and can be used
L2e
as a trend indicator in cases where the ISOMETER® has to adapt to an R
C
relation that varies considerably.
e
It is possible to assign the detected fault or the faulty conductor to an alarm
relay via the menu. If the values R
in the "AL" menu, this will be indicated by the LEDs and relays "K1" and "K2"
according to the alarm assignment set in the "out" menu. In addition, the
operation of the relay (n.o./n.c.) can be set and the fault memory "M", activat-
ed.
isoEV425_D00126_09_M_XXEN/03.2019
Display
-100 % one-sided fault at conductor L2/-
0 % symmetrical fault
+100 % one-sided fault at conductor L1/+
(between L1/+ and earth) and U
L1e
Description
= (200 % * R
L1F
R
= (200 % * R
L2F
from the residual voltages U
UGF
or U
violate the response values activated
F
n
and the system leakage
F
between L1/+ and L2/-
n
)/(100 % + R %)
F
)/(100 % – R %)
F
(be-
L2e
F
and
L1e
and
F
15