Modbus register assignment of the ISOMETER®
Property
Register
3020
RW
3021
RW
3022
RW
3023
RW
3024
RW
3025
RW
3026
RW
3027
RW
3028
RW
8003
WO
isoEV425_D00126_09_M_XXEN/03.2019
Description
Delay on release
"toff" for relays K1
and K2
Repetition time
"test" for auto-
matic
device test
Reserved
Reserved
Test of the sys-
tem connection
during device test
"nEt"
Device test dur-
ing device start
"S. Ct"
Request stop
mode (0 = deacti-
vate device)
Alarm assignment
of relay 1
"r1"
Alarm assignment
of relay 2
"r2"
Factory
setting for all
parameters
Unit
Format
UINT 16
s
UINT 16
---
---
---
---
---
UINT 16
---
UINT 16
---
UINT 16
---
UINT 16
---
UINT 16
---
UINT 16
---
Value range
0 ... 99
0 = OFF
1 = 1 h
2 = 24 h
---
---
0 = Inactive
1 = Active
0 = Inactive
1 = Active
0 = Stop
1 = ---
Bit 15 ... Bit 0
Bit 15 ... Bit 0
0x6661 "fa"
47