Message
AF Dim Removed
AF detects that a dimmer has been
<Dimmer Nr>
removed
AF Bkr Trip
AF detects that a dimmer circuit
<Dimmer Nr>
breaker has tripped
AF RCD Trip
AF detects that a dimmer circuit with
<Dimmer Nr>
RCD has tripped due to earth leakage
AF Load High
AF detects that the current load on a
<Dimmer Nr>
circuit is higher than the recorded load
AF Load Low
AF detects that the current load on a
<Dimmer Nr>
circuit is lower than the recorded load
AF No Load
AF detects that there is no load on a
<Dimmer Nr>
circuit
Dim Overtemp
An overtemperature condition has
<Dimmer Nr>
been detected on a dimmer module
Error Messages
Cause
Possible Corrective Action
Reinsert dimmer; check dimmer module
Reset circuit breaker; check dimmer module
Reset circuit breaker; check dimmer module and
load
Check load/lamps
Check load/lamps
Check load/lamps
Clear the error from the home screen and see if it
returns.
Check rack cooling fan is running and that room
is in recommended temperature range.
If normal temp, replace module.