Power Control Processor Mk2 For use with Echo Relay Panel Mains Feed, Echo Relay Panel Feedthrough, and the Sensor IQ Intelligent Breaker Panel Configuration Manual Version 4.0.0 Part Number: 7123M2410-4.0.0 Rev: A Released: 2023-03...
Page 2
To view a list of ETC trademarks and patents, go to etcconnect.com/ip. All other trademarks, both marked and not marked, are the property of their respective owners. For a complete list of all third-party licenses that are fully incorporated herein to the extent required by each third-party license terms and conditions please visit etcconnect.com/licenses.
Table of Contents Introduction Help from ETC Technical Services Document Conventions Chapter 1 Overview of Panels Echo Relay Panel Mains Feed Overview Echo Relay Panel Feedthrough Overview Sensor IQ Overview Option Cards 0–10V Dimming Control DALI Control Contact Input RideThru Option...
Page 4
Release Set Levels Arch Control Menu Presets Sequences File Operations Save Configuration Load Configuration Update Firmware Restore Defaults View Errors Chapter 4 Service and Maintenance Help from ETC Technical Services Maintenance Vacuum the Interior Replacing Fuses Power Control Processor Mk2 Configuration Manual...
Page 5
Appendix A Menu Flow Chart Appendix B Status Messages Emergency Active Breakers Tripped Relay Mismatch Relay Removed Breaker Mismatch Breaker Removed Breaker Error Table of Contents...
Page 6
Power Control Processor Mk2 Configuration Manual...
DMX-512 or Ethernet. Help from ETC Technical Services If you have questions that are not answered by this document, try the ETC support website at support.etcconnect.com or the main ETC website at etcconnect.com. If none of these resources are sufficient, contact ETC Technical Services directly at one of the offices identified below.
Page 8
26-28 Victoria Industrial Estate Room 1801, 18/F Victoria Road, Tower 1, Phase 1 Enterprise Square London W3 6UU England 9 Sheung Yuet Road +44 (0)20 8896 1000 Kowloon Bay, Kowloon, Hong Kong techservltd@etcconnect.com +852 2799 1220 techserv-asia@etcconnect.com Power Control Processor Mk2 Configuration Manual...
WARNING: RISK OF ELECTRIC SHOCK! This warning statement indicates situations where there is a risk of electric shock. All ETC documents are available for free download from our website: etcconnect.com. Please email comments about this manual to: TechComm@etcconnect.com.
Chapter 1 Overview of Panels The Power Control Processor Mk2 is designed for use in Echo Relay Panel Mains Feed, Echo Relay Panel Feedthrough, and Sensor IQ Intelligent Breaker System. Echo Relay Panel Mains Feed Overview The Echo Relay Panel Mains Feed (ERP) with Power Control Processor Mk2 provides professional-quality switching and dimming of loads controlled by DMX512 or Ethernet.
Echo Relay Panel Feedthrough Overview The Echo Relay Panel Feedthrough (ERP-FT) with Power Control Processor Mk2 provides professional-quality switching and dimming for up to 48 channels of non-dim loads in a single panel. Loads are controlled by DMX512 or Ethernet.
Sensor IQ Overview The Sensor IQ Intelligent Breaker System with Power Control Processor Mk2 provides professional-quality switching and dimming of loads controlled by DMX512 or Ethernet. A Install optional Main Circuit Breaker here B Main lugs C Breakers D Circuit breaker for the User Interface...
0–10V Dimming Control The 0–10V Dimming Control option provides 24 outputs for control of 4-wire current-sink, 0–10 VDC fluorescent or electronic loads. • Each of the 24 outputs are rated to control a maximum of 400 mA per channel (up to 50 ballasts per channel). •...
Echo station for direct control using that station's buttons or faders. You can have multiple zones within a space, and a single zone can control multiple outputs across mutliple panels. Power Control Processor Mk2 Configuration Manual...
Chapter 2 The User Interface The Power Control Processor Mk2 features a simple user interface with up and down arrows for menu navigation, a numeric keypad for direct selection, and an easy-to-read graphical display. Additionally, a USB port is provided on the left side of the controller for storage of configurations to a flash drive.
The Display The Power Control Processor Mk2 features a high-contrast, 21-character, 8-line, backlit screen. When scrolling through the menu, the first row of the display is reserved for the menu title.
Output Status The Output Status screen displays several lines of information: • Line 1 shows: Output Status ‐ The name of the display: Output Status ‐ An "L" symbol is shown when levels are set locally at the System OK panel. DMX Start = 101 DMX Input: Active ‐...
‐ sACN Input will be displayed as either Active , Inactive, or Disabled . • Line 8 shows the status of connected Echo power station status (On or Off) and the current Power Control Processor Mk2 software version number. Note: Echo power station support is reserved for later development.
Echo power station support is reserved for later development. USB Media The Power Control Processor Mk2 includes a USB type A socket located on the left side of the user interface. A USB storage device is not included and must be purchased sparately.
Output Count: Auto Press DMX Start Addr: DMX Start Addr: sACN Universe: sACN Universe: [Enter] sACN Start Addr: sACN Start Addr: Space: Space: (ü Apply Changes* Only Apply Changes* Only Apply All Apply All Power Control Processor Mk2 Configuration Manual...
Page 21
Multi-Part Options In a multi-part menu, press [Enter] (ü) to modify an editable item, then use the numeric keypad or[Up] ( ) or [Down] ( ) to enter the correct value. 1 AND 3 THRU 6 Patch sACN Input Patch sACN Input Address Univ Address...
Revers-phase dimming control. • Current Level displays the current level of the selected circuit from the controlling data source as a percentage (%). When no control is present, current level displays a dash (–). Power Control Processor Mk2 Configuration Manual...
• Load displays the load both as amperes (A) and calculated (VA). The load value displays and updates in real time. Multiple-pole relays will show load for each pole (load (1), load (2), etc.). ‐ For the Echo Relay Panel Feedthrough, voltage is not measured, and this field contains a dash (–).
• Zone allows configuration of the Zone to which the selected outputs are allocated. See Zones on page 9 • Circuit displays the currently assigned circuit number for the dimmer or relay position in the panel. Power Control Processor Mk2 Configuration Manual...
• Allow Manual determines what happens when a manual override occurs on products supporting manual override. ‐ Yes (default): the relay is treated as if the level has been set to full. ‐ No : When a manual override is attempted, the controller will reassert control and change the relay to the state requestedy by the incoming control inputs.
DMX Start Addr: unconfigured. sACN Universe: sACN Start Addr: Space: For additional setup or to quickly change a setting after initial Apply Changes* Only configuration, access Quick Rack Setup from the main menu. Apply All Power Control Processor Mk2 Configuration Manual...
Page 27
CAUTION: The "Quick Rack Setup" operation will erase your panel's configuration and generate a new one. ETC recommends making a backup of your configuration before entering this menu option. • Output Count: ‐ If you select Auto , the numbering and arrangement of the outputs is automatically detected by the presence or absence of breakers or relays.
Page 28
Space 1 2-Pole 1-Pole sACN ch 10 Set to: Set to: Channel 9 Channel 12 DMX 9 Position 11 Position 12 DMX 12 Space 1 2-Pole 1-Pole Space 1 sACN ch 9 sACN ch 12 Power Control Processor Mk2 Configuration Manual...
Switching Options The Switching Setup menu allows you to configure the switching Switching Options Relay Delay: delay and LatchLock settings. LatchLock On: 91-100% L/L On Time: • Relay Delay is the delay when outputs turn on, in LatchLock Off: 41-50% L/L Off Time: milliseconds.
Forever . • Fade Time is set in minutes and seconds. The range is from 0–59 minutes and 0–59 seconds. The default Fade Time is three seconds ( 0min 3sec ). Power Control Processor Mk2 Configuration Manual...
Power On Behavior Power On determines the behavior for the control when the Echo powers on. The options include Last-Look and Off . The default is Last-Look . • Last-Look : Relays remain in their positions from the last power cycle, when the controller was powered up, if there is no control source.
When you exit the Set Levels menu you will be prompted to Release Set Levels. • Select Yes to return all set levels to the default value. • Select No to cause all set levels to remain until released. Power Control Processor Mk2 Configuration Manual...
Output Check The Output Check menu allows you to check outputs individually. • Output defaults to position 1 . It is then possible to scroll Output Check through all outputs to perform a quick functionality check. Output: Check Level: 100% Output position numbers will roll over from one to the Next Output Previous Output...
Deactivate Fade up in Step 2 Fade down in Step Step1 Downtime Sequence is Hold for Step Hold for Step Sequence Uptime 2 Downtime finished " 2 Hold Time 1 Hold Time " " Power Control Processor Mk2 Configuration Manual...
Page 35
1. For example, if there are 3 steps in a sequence, the steps will run: 1, 2, 3, 1, 2, 3, 1, 2, 3, etc. The following example shows the activation and deactivation of a sequence with three steps in Loop mode.
Power Control Processor Mk2 ships with the current version of software installed. The firmware of your Power Control Processor Mk2 can be field-upgraded as needed. When new firmware is released, ETC Technical Services can supply the necessary files. Some USB keys may...
If you run into this situation, contact ETC Technical Services and request a USB upgrade Kit (ETC part number 7123K1024-4.0.0), which includes a known-working USB key. CAUTION: Updating firmware may cause outputs to change. Only perform firmware updates when it is acceptable for output levels to turn on or off.
Chapter 4 Service and Maintenance Help from ETC Technical Services If you have questions that are not answered by this document, try the ETC support website at support.etcconnect.com or the main ETC website at etcconnect.com. If none of these resources are sufficient, contact ETC Technical Services directly at one of the offices identified below.
Page 39
ETC, Inc. ETC GmbH Americas Germany, Austria, Switzerland, Eastern Europe, and Russia Technical Services Department 3031 Pleasant View Road Technical Services Department Middleton, WI 53562 Ohmstrasse 3 800-775-4382 (USA, toll-free) 83607 Holzkirchen, Germany +1-608 831-4116 +49 (80 24) 47 00-0 service@etcconnect.com...
Most faults should cause the associated circuit breaker to trip; however, very high current direct shorts may cause fuse failure. Two spare fuses are included inside the panel. The fuse is a 30A SC-30 (ETC part number F334). Replace the fuse with the same type only.
Appendix A Menu Flow Chart This appendix contains the Power Control Processor Mk2 menu structure: page 37 • About on • Switching Setup on page 38 • Arch Setup on page 39 ‐ Contact Input on page 40 • Switching Control •...
Page 42
Power Control Processor Mk2 Configuration Manual...
Two spare fuses are included inside the panel. The fuse is a 30A SC-30 type fuse, available from ETC with part number F334. Replace the fuse only with a fuse of the same type. Replacing Fuses on page 35...
A "Relay Mismatch" message indicates that there is a difference between the types of one or more relays in the configuration for the Power Control Processor Mk2 and the types of relays detected in the panel. This condition occurs when relays have been added or altered in the panel after configuration.