UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Figure 3-2 Reserved clearances (unit: mm)

3.3 Power Cables

The UPS can generate large leakage currents. A circuit breaker that provides leakage current
protection is not recommended.
Table 3-2
Table 3-2 Recommended cross-sectional areas of power cables
Item
One input One-input current (A)
Two
inputs
Issue 04 (2020-03-12)
lists the recommended cross-sectional areas of power cables.
Recommended
cross-sectional area
2
(mm
)
Two-input current (A)
Recommended
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-60K
400
L1
4 x 185
L2
L3
N
400
L1
4 x 185
3 Installation Preparations
UPS5000-E-80K
630
4 x 2 x 185
None