Ensure that the UPS IP address is unique on the network segment. Otherwise, the WebUI
display function may be abnormal.
Issue 04 (2020-03-12)
Set an Ethernet IP address that ranges from 0.0.0.0 to 255.255.255.255. The default value
is 192.168.0.10.
Subnet mask parameter
Set an Ethernet subnet mask that ranges from 0.0.0.0 to 255.255.255.255. The default
value is 255.255.255.0.
Gateway parameter
Set an Ethernet gateway that ranges from 0.0.0.0 to 255.255.255.255. The default value
is 192.168.0.1.
RS485 address/RS485 baud rate
Set an address that ranges from 1 to 254 for this port. RS485 baud rate depends on the
network management conditions.
Batt. temp. sensors
A maximum of four battery temperature sensors can be cascaded.
Start addr. of batt. temp. sensor
Set this parameter by using the dual in-line package (DIP) switch on the battery
temperature sensor. The address range is 16-28. Ensure that the address that you set on
the LCD is the same as that set for the DIP switch. Otherwise, communication fails.
BMUs
BMUs can be cascaded. A maximum of 12 BMUs can be cascaded.
BMU start address
Set the BMU start address through the DIP switch on the BMU to 112. Ensure that the
address that you set on the LCD is the same as that set for the DIP switch. Otherwise,
communication cannot be implemented.
Amb. temp & humid sensors/Start addr. of amb. temp. & hum. sensors
An ambient temperature and humidity sensor has the same appearance as a battery
temperature sensor. The two types of sensors (up to four) can be cascaded. The ambient
temperature and humidity sensor address range is 32-44, which is different from the
battery temperature sensor. Therefore, you can use the sensor as an ambient temperature
and humidity sensor or battery temperature sensor by setting the address.
CIMs
Set this parameter to the number of connected CIMs. A maximum of four CIMs can be
connected.
CIM start address
Set this parameter to the communications address of the first connected CIM. The
address cannot be changed. The DIP switch should be set to 0000 for the first CIM, and
the DIP switch setting for a later connected CIM should increase by 1 (binary) than that
set for the previous CIM. For details, see the document delivered with the device.
NTC
The short-distance battery temperature sensor monitors the ambient temperature near
batteries. It ensures that batteries work reliably and securely. The default status is
Disable. If a short-distance battery temperature sensor is configured, set NTC to Enable.