UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Advanced Parameter Settings
Set System capacity and Power module capacity according to specifications. Incorrect
settings may cause an overload alarm, which affects normal UPS running.
Set advanced parameters, such as UPS model, System capacity, and Power module
capacity.
Figure 5-36 Advanced Param. screen 1
Issue 04 (2020-03-12)
A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V. The number of cells must be a multiple of 12 (for
example, 96 and 120).
Cell float voltage, Cell equalized volt, Float volt. temp. comp. coef., and EOD voltage threshold
are set for cells.