Huawei UPS5000-E-80K-LABBS User Manual page 214

Integrated ups, 208 v
Hide thumbs Also See for UPS5000-E-80K-LABBS:
Table of Contents

Advertisement

UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
0011-1
Bypass ph.
reversed
0012-1
Bypass
neutral
absent
0020-1
Battery
connected
reversely
0021-1
Battery
EOD
0022-1
No battery
Issue 04 (2020-03-12)
Severity
System Action
1. The system
Minor
cannot transfer
to bypass
mode.
2. The system
transfers to a
working mode
based on the
current power
supply status
and logic.
1. The system
Minor
cannot transfer
to bypass
mode.
2. The system
transfers to a
working mode
based on the
current power
supply status
and logic.
Critical
None.
Critical
The system
delivers a
shutdown
command because
the battery voltage
is low.
Minor
The monitoring
system delivers a
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
The phase
Check whether the cable
sequence of the
phase sequence is correct
three-phase bypass
based on the phase
input is reversed.
sequence table. If no
phase sequence table is
available, exchange the
positions of any two
cables.
1. Secure or connect the
The neutral wire of
bypass input is
absent.
2. Check that the neutral
1. Check whether
Batteries are not
properly installed.
2. Check whether the
The battery voltage
If the BCB-BOX is
reaches the EOD
configured, check
voltage threshold
whether the BCB-BOX
due to continuous
trips. If it trips, turn on
discharge.
the BCB-BOX switch.
1. Check that battery
There is no
battery string.
C Alarm List
frequency range
configured on the
LCD.
neutral wire to the
cabinet if it is loose
or disconnected.
wire to the power
distribution system is
normal.
battery polarities are
correctly installed by
using a multimeter. If
no, correct the
installation.
battery input voltage
of the UPS is normal.
If yes, the battery
sampling circuit of
the power module is
faulty. Replace the
power module.
cables are correctly
206

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-60k-lasbs

Table of Contents