2.3.4.2 ATS Controller
Figure 2-23
Figure 2-23 ATS controller
(1) Alarm ID description
Table 2-11
Table 2-11 Alarm ID description
Alarm ID
1
2
3
4
5
6
Issue 04 (2020-03-12)
After you pull out the handle, flip the electric/manual mode selection handle upwards to
the M position.
shows an ATS controller.
describes the alarm IDs of the ATS controller in detail.
Power
Supply
Status
No voltage
Undervoltage
Overvoltage
Phase
missing
Voltage
unbalance
Incorrect
phase
Copyright © Huawei Technologies Co., Ltd.
(2) Controller buttons
Description
The supply voltage is less than 10% of the rated voltage.
The supply voltage is less than the undervoltage threshold.
The supply voltage is greater than the overvoltage threshold.
A phase of the power supply is open.
The difference between the minimum and maximum phase
voltages of the power supply exceeds the percentage of the
overvoltage or undervoltage threshold.
The phase sequence of the power supply is incorrect.