UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Bus Capa. Life
Figure 5-71 Bus Capa. Life screen
Reset
After the service life of a capacitor is about to end, you need to manually remove it and
replace it with a new capacitor. After the new capacitor is installed, the power module cannot
detect the replacement, and you need to manually reset the service life of the new capacitor.
Reset PDU Address
After you tap this icon, the UPS reallocates a CAN address to the power distribution board
based on the actual address of the board.
5.1.2.6 About Screen
On the System Info screen, tap About On the About screen, you can view the UPS model,
manufacturer name, monitoring version and power version. To view version details, tap
Version Info.
Figure 5-72 About screen
Issue 04 (2020-03-12)
Copyright © Huawei Technologies Co., Ltd.
5 User Interface
130