Summary of Contents for Huawei UPS5000-E-25 kVA-BF
Page 1
2. Use insulated tools when installing the equipment. 3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
Installing the UPS 1. Determine the mounting holes based on 2. Adjust the anchor bolts and ensure that the the marking-off template, drill holes, and anchor bolts touch the floor. Then level the install expansion sleeves. UPS. Unit: mm 3. Remove the rear cover from the cabinet, 4.
Connecting Cables UPS Cable Connection Reference • Prepare cables away from the cabinets to prevent scraps from falling inside. Cable scraps may ignite and cause personal injury or device damage. • After cables have been installed, clean the cabinets in a timely manner. Keep the cabinets and surrounding environment clean and tidy.
Page 4
3. Connect the ground cable and power cables. Silk Port Bolt Torque Screen Description Specifications 4. Connect the signal cable. 1L1, 1L2, 26 N•m Input M10x30 1L3, N 46 N•m +, N, - Battery input M12x45 26 N•m U, V, W, N Output M10x30 13 N•m...
Page 5
Installing Battery Modules 1. Before installing battery modules, carefully read the battery safety precautions. 2. Place the battery modules in a correct way to prevent vibrations and shocks. 3. Install the battery modules from the lower layer to the upper layer to prevent falling over due to top-heaviness.
Close the upstream bypass and mains input switches. (Full configuration model) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
Page 7
Starting the Inverter Number of Battery Strings Battery Specifications Battery Capacity Connected in Parallel to the UPS 9 Ah/12 V 9 Ah + 9 Ah = 18 Ah 9 Ah/12 V 9 Ah + 9 Ah + 9 Ah = 27 Ah 9 Ah/12 V 9 Ah + 9 Ah + 9 Ah + 9 Ah = 36 Ah Initial Startup...
Page 8
Download the mobile phone app (Service Expert). Use the app to start the inverter No, start online? the inverter offline Insert the WiFi module into the USB port on On the MDU, choose System Info > the MDU. Maintenance > Inv. ON and obtain the Bar code and Verification code.
Shutting Down the UPS After you shut down the inverter, the UPS transfers to bypass mode if the bypass is normal; the UPS supplies no power if the bypass is abnormal. Before shutting down the UPS, ensure that all loads have been shut down. Shutting Down the Inverter to Transfer the UPS to Bypass Mode 1.
Page 10
3. Install batteries and cables, and bind cables. Connect the cable between the two batteries in the middle of the battery string at last so that a battery loop is not formed and operations can be performed with power off during cable connection.
Page 11
Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: http://support.huawei.com/enterprise http://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...