UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Settings on the LCD
Step 1 Set the master BSC system. On the main menu of the LCDs of the UPS, choose System
Info > Settings. Tap Advanced Param. on the Settings screen. On the displayed screen, set
BSC mode to BSC master mode.
Figure 6-15 BSC master mode
Step 2 Set the slave BSC system. On the main menu of the LCDs of the UPS, choose System Info >
Settings Tap Advanced Param. on the Settings screen. On the displayed screen, set BSC
mode to BSC slave mode.
Figure 6-16 BSC slave mode
Step 3 If no alarm is generated after settings, the UPS runs properly.
----End
Issue 04 (2020-03-12)
If you have not logged in, enter a user name and password, and tap
screen.
Copyright © Huawei Technologies Co., Ltd.
6 Operations
on the displayed login
159