UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Figure 6-39 Hibernation parameters on the WebUI
Step 3 On the WebUI, select Enable from the Paral. sys. hibernate drop-down list box and click
Submit. A message indicating that there is a risk is displayed. Click OK.
Step 4 Set the module cycle hiber. period to an integer ranging from 1 to 100. The default value is
30.
----End
Issue 04 (2020-03-12)
Click Submit after you set the parameter on the WebUI.
Copyright © Huawei Technologies Co., Ltd.
6 Operations
177