UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
0530-1
Battery
ground
fault
0032-1
Battery
overvoltag
e
protection
0036-2
Battery
maintenan
ce
reminder
Issue 04 (2020-03-12)
Severity
System Action
Critical
The system
generates alarm
information and
causes the BCB to
trip if the BCB is
ON.
1. The system
Critical
shuts down the
charger.
2. Hardware may
be damaged. In
addition, the
discharger
cannot be
started. If the
mains is
abnormal, the
system will
transfer to
bypass mode
or shut down
based on logic.
Warning
None.
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
1. Check whether the
The battery
string is not
properly
grounded.
The battery
ground
monitoring
2. Check whether the
cable is faulty.
The dry contact
board is faulty.
3. If no battery
1. Check the battery
The battery
voltage is
greater than the
2. Check that the
upper
threshold.
The configured
3. Check that the actual
number of
batteries is less
than the actual
number.
The actual
number of
batteries does
not meet
requirements.
The time for
Maintain the batteries.
maintenance
arrives.
C Alarm List
module.
positive and negative
terminals of the
battery string are
grounded or have
sufficient resistance
to the ground.
battery grounding
failure detector is
faulty by replacing it
with a new one.
grounding failure
detector is available,
check on the dry
contact board whether
the battery grounding
failure detector is
enabled. If yes,
disable it and check
whether the alarm is
cleared. If the alarm
persists, the dry
contact board may be
faulty. Replace the
board.
voltage.
configured number of
batteries matches the
actual number.
number of batteries
meets requirements.
208