Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
misoperati
on
0380
In
self-check
0148
ATS fault
0103
Input SPD
alarm
0349
Cabinet
input
breaker
open
0193
Mains
three-phas
e current
imbalance
0009
Mains
overload
0196
Branch
overload
0197
Mains
overcurren
t
0198
Branch
Current
High
0199
Mains
undercurre
nt
0200
Branch
Issue 04 (2020-03-12)
Severity
System Action
mode.
Warning
None.
Minor
None.
Minor
None.
Minor
None.
Warning
None.
Minor
None.
Critical
None.
Minor
None.
Minor
None.
Warning
None.
Warning
None.
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
2. After maintenance,
The inverter is in
Wait until the inverter
self-check.
self-check is complete.
ATS
communication
s parameters
are modified.
ATS cables are
disconnected.
The ATS is
faulty.
The input SPD is
Check the input SPD.
faulty.
The mains input
Turn on the mains input
circuit breaker.
circuit breaker is
OFF.
The load power
Check the load.
among three
phases is
unbalanced.
Phase L1, L2, or
Check phase A loads.
L3 is overloaded.
A branch is
Check the branch loads.
overloaded.
Phase L1, L2, or
Check phase L1, L2, or
L3 loads.
L3 experienced
overcurrent.
A branch
Check the branch loads.
experienced
overcurrent.
Phase L1, L2, or
Check phase L1, L2, or
L3 loads.
L3 experienced
overcurrent.
A branch
Check the branch loads.
C Alarm List
on the maintenance
circuit breaker.
turn off the
maintenance circuit
breaker and then start
the inverter.
Restore the ATS
communications
parameters to default
values.
Check the
communications
cable connections.
Check the ATS.