UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
0047-1
Not ready
0060-4
Inverter
abnormal
0061-7
Inverter
alarm
0564-1
Overload
timeout
Issue 04 (2020-03-12)
Severity
System Action
Critical
None.
1. If the module
Critical
works in
inverter mode,
the module
stops output.
2. If the module
works in
non-inverter
mode, the
module cannot
transfer to
inverter mode.
1. The system
Minor
shuts down the
module.
2. If only one
module is
working, or the
system will be
overloaded
after the
module shuts
down, the
system will
transfer to
bypass mode
or shut down
based on logic.
The system
automatically
starts after the
fault is
rectified.
1. If the bypass
Critical
can supply
power, the
system
transfers to
bypass mode.
Five minutes
later, the
system
automatically
switches back
to inverter
mode.
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
The ready switch
Turn on the ready switch.
is OFF.
1. Check load cable
A load
short-circuit
occurs.
2. If load cable
A short circuit
occurs inside
the module.
The fault
seldom occurs.
1. If not all modules
The bypass
waveform is
abnormal.
2. If all modules
1. Check that there is no
The load is
excessive.
2. Check that the
Derating
reduces the
rated system
power.
3. If the alarm persists,
The module is
damaged.
C Alarm List
connections.
distributions are
normal, replace the
power module.
generate the alarm,
start the UPS and
transfer it to normal
mode and replace the
faulty module.
generate the alarm,
open the bypass input
circuit breaker. After
the inverter relay is
closed, close the
bypass input circuit
breaker 10 seconds
later.
overload.
module power is not
derated due to a fan
fault.
replace the power
module.
210