UPS5000-E-(20 kVA-80 kVA)
User Manual (Integrated UPS, 208 V)
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
undercurre
nt
0370
Branch
switch
open
0203
Branch
switch
abnormal
0211
ATS
non-auto
mode
0212
Main
temperatur
e abnormal
0213
Branch
temperatur
e abnormal
0216
ATS
backup
power
abnormal
Issue 04 (2020-03-12)
Severity
System Action
Critical
None.
Warning
None.
Minor
None.
Critical
None.
Critical
None.
Critical
None.
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
experienced
overcurrent.
A branch switch is
Check the status of the
OFF.
branch switch.
A branch is not
Check the branch loads.
connected to loads.
The ATS
Set the ATS switchover
mode to automatic mode.
switchover mode
is set to manual
mode.
Overload for a
long time
Unreliable
copper bar
connection
Overload for a
long time
Unreliable
copper bar
connection
Fire
One ATS power
Check whether two ATS
supply is
power inputs are normal.
abnormal.
C Alarm List
Check that there is no
overload.
Power off the UPS
and check whether
the copper bar is
reliably connected.
Check whether there
is a branch fire.
Check that there is no
overload.
Power off the UPS
and check whether
the copper bar is
reliably connected.
216