Step 2 After the inverter shuts down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power, and the loads shut down.
Issue 04 (2020-03-12)
b.
If you have not logged in, enter a user name and password, and tap
the login screen displayed.
c.
In the displayed dialog box, tap Yes to shut down the inverter.
Figure 6-19 Inverter Off screen
You can also tap System Info > Maintenance and shut down the inverter on the Maintenance screen.
Method for shutting down the inverter on the WebUI
a.
In a web browser, enter the UPS IP address.
b.
On the login page, select a display language, enter a user name and password, and
click Login.
c.
On the homepage, choose Monitoring > Control, and click Inv. OFF. In the
displayed dialog box, click OK to shut down the inverter.
Figure 6-20 Shutting down the inverter
To shut down the inverter and transfer the system to bypass mode, perform only
ensure that the UPS generates no alarm.
To power off the entire UPS, perform all the preceding steps.