Walk Test™Procedures, Continued
How to Enter Walk
Test Mode
The Walk Test™ Settings menu allows the settings for each group to be individually adjusted.
Use the <Next Group> or <Prev Group> soft keys to step through the Walk Test groups 0 to 7.
The list rolls around in either stepping direction.
For each Walk Test group the current settings are displayed:
The settings are:
Status – is this Walk Test group On or Off?
Logging – will test alarms in the group be recorded in the system log or not? Generally,
the Log option should be selected.
Coding – if the sounders are enabled, will they do Zone coding or just a simple
"0 CODE". If the Signalling option is set to Silent, the Coding setting does not matter.
Signalling – will the sounders for this group activate on a test alarm (be Audible) or stay
Silent. Generally, the Silent option should be selected.
To change any setting on the currently displayed Walk Test group, use the Up or Down keys
to scroll the highlight to the setting to change, and press <Select Item> or <ENTER>.
In the settings display, the highlight shows the current setting. Use Up or Down to move the
highlight to the other setting, then <Select Item> soft key to change it.