Alarm And Fault Test For Zones; Alarm Test; Fault Test - Tyco 4100ES Operator's Manual

Fire indicator panel
Table of Contents

Advertisement

Alarm and Fault Test for Zones

Alarm Test

Alarm Test forces a zone into the alarm state. Once the zone is in alarm, you can check to see if
the system reacts in the way that it has been programmed, i.e., do signals sound in the correct
manner? do relays function correctly? etc.
Note: When you force a zone into alarm, if the zone is not isolated, then any outputs that are
programmed to activate on alarm will activate: Brigade signalling, Warning System, etc.
Follow these steps to perform an alarm test on a zone:
1.
2.

Fault Test

The fault test allows you to simulate a fault condition on a zone. This allows you to test the
manner in which the FIP reacts to the fault, e.g., verify the operation of the brigade interface.
Note: When you force a zone into fault if the zone is not isolated then any outputs that are
programmed to activate on fault will activate, including Brigade signalling.
Follow these steps to perform a fault test on a zone:
1.
2.
Note: The Alarm or Fault Test function will be cancelled if the Alarm/Fault Test key is pressed
again, or after 1 minute of no testing.
Press the <ALARM/FAULT TEST> key. The ALARM TEST LED will turn on.
Figure 5-1. Ready for Zone Alarm Test
While the ALARM TEST LED is on, press the appropriate Zone Isolate key (see the next
section). This zone will go into alarm: the corresponding red Zone Alarm LED will turn on,
along with the Fire Alarm display on the main screen.
Press the <ALARM/FAULT TEST> key until "FAULT TEST READY" is displayed. The
FAULT TEST LED will turn on.
Figure 5-2. Ready for Zone Fault Test
While the FAULT TEST LED is on, press the appropriate Zone Isolate key on the zone
display panel (see the next section).
5-2

Advertisement

Table of Contents
loading

Table of Contents