Acknowledging Fault or Isolate Conditions, Continued
Panel Operating
Procedure – Fault
Condition
Resetting Fault
Conditions
1.
Unlock and open the panel door. The yellow Fault or Isolate indicator (LED) will be
flashing and the sounder (buzzer) sounding.
2.
Press the <FAULT ACK> or <ISOLATE ACK> key as appropriate. An
acknowledgement message is displayed (this example for Isolate):
Figure 3-2. Operator Interface Showing Isolate Acknowledgement
After the acknowledgement, the list of Faults or Isolates is displayed, with the earliest Fault or
Isolate at the top of the list.
Most faults automatically clear from the system when the problem causing the fault (wiring,
device, etc.) has been fixed.
Some faults, such as open circuit faults on IDNet communications lines, latch until they are
reset manually or cleared by pressing the <SYSTEM RESET> key once the fault condition
has been fixed.