Enabling a
To enable a point:
Point
1.
2.
Note: The system displays a message indicating that the point will be enabled in 60
seconds, and counts down. If the state of the device is such that an alarm condition will
occur when the point is enabled, the system warns you that this will happen.
You can abort the enable operation before the countdown timer expires by pressing the
<DISABLE> soft key.
You can make the enable happen immediately by pressing the <ENTER> key during the
count down.
Select the disabled point that you want to enable, e.g., by selecting the point directly, or
by scrolling through the Fault list to find it.
Press the <ENABLE> soft key.
Figure 5-6. Count down message during enabling a point
5-5