Annual Tests, Continued
CAUTION: TAKE PRECAUTIONS TO PREVENT UNACCEPTABLE VENTILATION
Annual Tests -
SYSTEM CHANGES
Smoke Hazard
Management
Additional Tests to be Done Annually - Smoke Hazard Management Systems
Systems
AS 1851
Item No.
3.19
3.20
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.27
Description
Action Required and Pass/Fail
Criteria
FFCP latching and
CHECK that after initiation by a signal
reset
from the FIP, the FFCP remains
operating in the fire mode until reset by
the reset switch on the FFCP.
Manual override
CHECK that manual override ON-
controls
AUTO-OFF control operates.
NOTE: Manual override should
function in normal mode and fire mode.
Manual override
CHECK that manual override ON-
controls
AUTO-OFF control operates.
NOTE: Manual override should
function in normal mode and fire mode.
Airflow fault
CHECK the operation of the airflow
indicator
fault indicator
Open-circuit fault
CHECK the operation of the air-
indicator
handling equipment interconnecting
cable open-circuit fault indicator.
Closed-circuit
CHECK the operation of the air-
fault indicator
handling equipment interconnecting
cable closed-circuit fault indicator.
Electrical
CHECK the operation of the electricity
phase-fail fault indicator.
Fan-running
CHECK the operation of the fan-
indicator
running indicator.
Fan-stopped
CHECK the operation of the fan-
indicator
stopped indicator.
Fan fault indicator
CHECK the operation of the fan-fault
indicator.
12-4
Test Facility, Procedure,
Notes
Trigger the FFCP with a zone
alarm test on the FIP (Chapter
5).
Then reset the FIP and check
the FFCP is still operating in
fire mode.
Press A/C Auto Reset control
to clear.
Check operation between the
FFCP and the field equipment.