4100ES Fire Indicator Panel Operator's Guide
Fire detectors in the building are grouped into zones (searchable areas).
Zones can be Isolated by pressing the zone's isolate pushbutton on the panel – this prevents an
alarm from activating the panel outputs.
When a non-isolated detector detects an alarm, the fire panel displays the alarm information, calls
the fire brigade, activates the Warning or Evacuation System (EWS), and initiates any other
programmed functions.
The fire panel display consists of two sections – the operator interface (upper section) and the Zone
Isolate pushbutton switches & indicators (lower section).
The operator interface indicates common Alarm, Fault & Isolation Status on LEDs, and point
(detector) status on the LCD.
When an Alarm, Fault or Isolation occurs, the buzzer will operate until the corresponding
acknowledge (Ack) key is pressed.
Silence the External Bell or Strobe: Press the
<EXT BELL ISOLATE> key.
Silence the Evacuation System: Press the
<WARN SYS ISOLATE> key. This will turn off warning
sounders powered by the Fire Panel.
Isolate a Zone: Press the appropriate Zone Isolate
pushbutton and the Isolated LED for that zone will turn on.
Acknowledge an Isolation: Press the <ISOLATE ACK>
key.
Acknowledge an Alarm: Press the <FIRE ALARM ACK>
key.
Acknowledge a Fault: Press the <FAULT ACK> key.
The panel is reset by pressing <SYSTEM RESET>. If an alarm won't reset, the point may still be
activated. Press <FIRE ALARM ACK> when the point alarm is displayed, then press <DISABLE>,
<ENTER>. Press <FAULT ACK> (to acknowledge the fault caused by disabling a point), then press
<SYSTEM RESET> again. The disabled detector must be re-enabled when the condition is cleared.
Operator Interface
Zone Isolate
Pushbuttons