Printing A Report; Procedure - Tyco 4100ES Operator's Manual

Fire indicator panel
Table of Contents

Advertisement

Printing a Report

Overview

Procedure.

The system can generate any of the following reports.
Report
Alarm Log
Fault Log
TrueAlarm Status
TrueAlarm Service
TrueAlert NAC Test,
True NAC Status
TrueAlarm CO
Print an active list
The report prints on the panel's report printer if this is defined in the configuration.
The report output can also be conveniently captured via the Ethernet connection to the service
port on the 4100ES. Refer to LT0565 4100 Fault Finding Guide for details about this.
Description
Report includes all information contained in the alarm
history log – device custom label, time and date device
entered alarm.
Report includes all information contained in the fault
history log – device custom label, type of trouble, time
and date device experienced trouble.
Reports the following information for each point.
Device Number
Custom Label
Current Sensitivity of the Point
Point Status: Normal, Fault, Alarm
Almost Dirty Status: Points which are almost dirty
have an asterisk in this field to denote this.
Reports the following information for each point.
Device Number
Custom Label
Alarm Level (sensitivity level of the device)
Average Value –
Current Value --
Percent of Alarm: Shows the current value for the
sensor as a percentage of the alarm level. For
example, if the value shown is 9%, it means that the
sensor is currently at 9% of the value required to
trigger an alarm.
Peak Value. Shows the highest value that the
sensor has reached. Value is shown as a
percentage of 100 percent (alarm). For example, if
the value shown is 9%, it means that the peak value
experienced by the sensor was 9% of the value
required to trigger an alarm.
Current State: Possible values include Normal,
Fault, Dirty, Excessively Dirty, and Almost Dirty.
These reports are not relevant for Australian
installations of 4100ES.
These detectors are not used in Australia.
Prints all control (output) points that are off normal.
This can be useful during system testing.
11-3