Model DPV-1 Dry Pipe Valve
Model ACC-1 Dry Pipe Valve Accelerator
European Conformity Valve Trim
General
Description
Dry Pipe Valve
The TYCO Model DPV-1 Dry Pipe Valve
is a differential valve for automatically
controlling the flow of water into dry
pipe fire protection sprinkler systems
upon operation of one or more auto-
matic sprinklers. The Model DPV-1 Dry
Pipe Valve also provides for actuation
of fire alarms upon system operation.
The valve is available in four sizes:
DN65, DN80, DN100, and DN150.
Features for the Model DPV-1 Dry Pipe
Valve are as follows:
• External reset
• 16 bar pressure rating
• Unique offset single clapper design
enabling a simple compact valve to
minimize installation labor
• Ductile iron construction to ensure
a lightweight valve to minimize ship-
ping cost
• A variety of inlet and outlet
connections
• Simple reset procedure through the
elimination of priming water
Dry pipe sprinkler systems are used
in unheated warehouses, parking
garages, store windows, attic spaces,
loading docks, and other areas
exposed to freezing temperatures,
where water filled pipe cannot be uti-
lized. When set for service, the dry
pipe sprinkler system is pressurized
with air (or nitrogen). The loss of pres-
sure through an operated automatic
sprinkler in response to heat from a
fire permits the Model DPV-1 Dry Pipe
Valve to open and allow a flow of water
into the sprinkler system piping. Table
B establishes the minimum required
system air pressure that includes a
safety factor to help prevent false oper-
ations that occur due to water supply
fluctuations.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Page 1 of 26
Accelerator
The optional TYCO Model ACC-1
Dry Pipe Valve Accelerator is a quick
opening device that is intended to
reduce the time for valve operation fol-
lowing the operation of one or more
automatic sprinklers. The Model ACC-1
Accelerator automatically adjusts to
both small and slow changes in system
pressure, but trips when there is a rapid
and steady drop in pressure (as in the
case of a sprinkler operation). Upon
tripping, the Accelerator transmits
system air pressure to the intermediate
chamber of the Model DPV-1 Dry Pipe
Valve. This neutralizes the differen-
tial pressure holding the Model DPV-1
Dry Pipe Valve closed and permits it
to open.
The Model ACC-1 Dry Pipe Valve
Accelerator has a unique, positive
action, internal anti-flood device and
a ball float which combine to prevent
water and water borne debris from
entering the more sensitive operating
areas of the accelerator. The anti-flood
device seals and latches immediately
upon operation of the Model ACC-1 Dry
Pipe Valve Accelerator without waiting
for a pressure build-up in the intermedi-
ate chamber of the Dry Pipe Valve. The
latching feature keeps the anti-flood
device sealed, even while the system
is being drained. The ball float seals the
pilot chamber inlet port if there is an
inadvertent trip of the Dry Pipe Valve,
due for example, to an air compressor
failure combined with a slow loss in
system air pressure due to a leak.
NOTICE
The Model DPV-1 Dry Pipe Valves and
Model ACC-1 Dry Pipe Valve Accelera-
tors described herein must be installed
and maintained in compliance with this
document and the standards recog-
nized by the Approval agency, in addi-
tion to any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
JULY 2020
Worldwide
www.tyco-fire.com
Contacts
Nominal
Alarm
With
Valve
Test
Accelerator Figure
Size
Valve
Three
Way
DN65
Standard
Three
Way
DN80
Standard
Three
Way
DN100
Standard
Three
Way
DN150
Standard
TABLE A
EUROPEAN CONFORMITY
VALVE TRIM CONFIGURATIONS
7
13
10
16
7
13
10
16
8
14
11
17
12
15
10
18
TFP1090

Advertisement

loading

Summary of Contents for Tyco DPV-1

  • Page 1 Dry Pipe Valve lowing the operation of one or more The TYCO Model DPV-1 Dry Pipe Valve automatic sprinklers. The Model ACC-1 is a differential valve for automatically Accelerator automatically adjusts to...
  • Page 2 Reset Plunger Parts Kit Includes Items 11-18 92-312-1-405 Reset Knob, Item 11 . . . 92-312-1-406 Reset Plunger O-Ring, Item 15 ..92-312-1-407 FIGURE 1A MODEL DPV-1 DRY PIPE VALVE DN65, DN80 AND DN100 ASSEMBLY...
  • Page 3 ..92-312-1-604 Reset Plunger Parts Kit Includes Items 14-21 92-312-1-405 Reset Knob, Item 14 . . . 92-312-1-406 Reset Plunger O-Ring, Item 18 ..92-312-1-407 FIGURE 1B MODEL DPV-1 DRY PIPE VALVE DN150 ASSEMBLY...
  • Page 4: Technical Data

    The difference is such that the Model or without the TYCO Model ACC-1 Figures 7 through 18. See Table A. The DPV-1 has a nominal trip ratio of 5.5:1 Dry Pipe Valve Accelerator are FM, Valve Trim forms a part of the labora- (water to air).
  • Page 5 Page 5 of 26 flows through the Alarm Port as shown 0,60 in Figure 3B at the rear of the Model DPV-1 Dry Pipe Valve. As the flow 0,50 through the Alarm Port exceeds the drain capacity of the Automatic Drain...
  • Page 6 PORT ASSEMBLY DRAIN RESEATED PORT WATER SUPPLY WATER SUPPLY SHUT OFF SHUT OFF FIGURE 3D FIGURE 3E DRAIN POSITION RESET POSITION FIGURE 3 (PART 1 OF 2) MODEL DPV-1 DRY PIPE VALVE PHASES OF OPERATION DN65, DN80 AND DN100 VALVES...
  • Page 7 CLAPPER LATCH CLAPPER MAIN ASSEMBLY DRAIN RESEATED PORT WATER SUPPLY WATER SUPPLY SHUT OFF SHUT OFF FIGURE 3D FIGURE 3E DRAIN POSITION RESET POSITION FIGURE 3 (PART 2 OF 2) MODEL DPV-1 DRY PIPE VALVE PHASES OF OPERATION DN150 VALVE...
  • Page 8 TFP1090 Page 8 of 26 Replacement Part Kits Description DESCRIPTION QTY. Repair Parts Includes Items 5, 6, 8, 10, 11, 23, 27 92-311-1-116 Base Kit (a) & 1.5 grams of FS3452 Cover Replacement Include Items 4, 13-22, 29 92-311-1-117 Upper Diaphragm Parts Kit (b) &...
  • Page 9 TFP1090 Page 9 of 26 RESTRICTION 1/4" NPT GAUGE CONNECTION DIFFERENTIAL CHAMBER PILOT SPRING CHAMBER ANTI-FLOOD VALVE BALL FLOAT 1/2" NPT INLET PILOT CHAMBER RELIEF VALVE INLET PORT EXHAUST VALVE INLET CHAMBER OUTLET CHAMBER 1/2" NPT OUTLET FIGURE 5 MODEL ACC-1 DRY PIPE VALVE ACCELERATOR IN SET POSITION PLUNGER LATCH...
  • Page 10: Installation

    4°C. and close the Air Supply Control Valve. 14,1 3,4 - 4,0 If the Model DPV-1 Dry Pipe Valve is Heat tracing of the Model DPV-1 Valve 15,5 3,8 - 4,3 equipped with a Dry Pipe Valve Accel-...
  • Page 11: Care And Maintenance

    Step 10B. Slowly remove the Vent If there are no leaks, the Model DPV-1 least once a year as follows: Plug located in the front of the Accel- Dry Pipe Valve is ready to be placed erator Cover and bleed off any resid- Step 1.
  • Page 12 If leakage is present, take the Model Accelerator trip is essentially the same Step 4. Clean the Clapper Facing, DPV-1 Valve out of service (that is, as in previous tests. A momentary Clapper, and Clapper Facing Retainer, close the Main Control Valve, open...
  • Page 13 ..... . 59304FO Manifold, Model DPV-1 Dry Pipe Valve, Groove x Groove 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets ..
  • Page 14 ..... . 59304FO Manifold, Model DPV-1 Dry Pipe Valve, DN100, Groove x Groove ..523091923 1"...
  • Page 15 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets ..MANIF3WAY Model DPV-1 Dry Pipe Valve, DN150, Groove x Groove ..523131960 Elbow, DN20 Male Thd x DN20 Female Thd .
  • Page 16 ..RTDMBFN Model DPV-1 Dry Pipe Valve, Groove x Groove Plug, DN15 Male Thd ....... . .
  • Page 17 ....... . . PTDN Model DPV-1 Dry Pipe Valve, DN100, Groove x Groove ..
  • Page 18 ....... . . PTDN Model DPV-1 Dry Pipe Valve, DN150, Groove x Groove ..
  • Page 19 ..MANIF3WAY Model DPV-1 Dry Pipe Valve, Groove x Groove Ball Valve, 3-way, 1/2" BSP ......
  • Page 20 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets ..MANIF3WAY Model DPV-1 Dry Pipe Valve, DN100, Groove x Groove ..523091923 Ball Valve, 3-way, 1/2" BSP .
  • Page 21 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets ..MANIF3WAY Model DPV-1 Dry Pipe Valve, DN150, Groove x Groove ..523131960 Elbow, DN20 Male Thd x DN20 Female Thd .
  • Page 22 ....523111001 Manifold, Model DPV-1 Dry Pipe Valve, Groove x Groove 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets ..
  • Page 23 ....... PCTDN Model DPV-1 Dry Pipe Valve, DN100, Groove x Groove ..
  • Page 24 ....523111001 Manifold, Model DPV-1 Dry Pipe Valve, DN150, Groove x Groove ..523131960 1" BSP Female Thd, 3 x 1/2" BSP Female Thd Outlets .
  • Page 25: Limited Warranty

    Standard Alarm Test Valve 88,9 mm DN100 114,3 mm DN150 168,3 mm 165,1 mm TABLE E MODEL DPV-1 DRY PIPE VALVE WITH EUROPEAN CONFORMITY TRIM FULLY TRIMMED VALVE ASSEMBLIES PART NUMBER SELECTION Limited Ordering Accessories Specify: (description) for use with Warranty...
  • Page 26 TFP1090 Page 26 of 26 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...
  • Page 27 Appendix A of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN65 and DN80, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, without Model ACC-1 Accelerator 426 mm 422 mm 367 mm 185 mm I. Normal Conditions III.
  • Page 28 Appendix B of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN100, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, without Model ACC-1 Accelerator 440 mm 395 mm 376 mm 185 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 29 Appendix C of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN150, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, without Model ACC-1 Accelerator 480 mm 399 mm 346 mm 191 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 30 Appendix D of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN65 and DN80, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, without Model ACC-1 Accelerator 426 mm DN65 = 416 mm DN80 = 396 mm...
  • Page 31 Appendix E of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN100, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, without Model ACC-1 Accelerator 440 mm 407 mm 376 mm 193 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 32 Appendix F of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN150, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, without Model ACC-1 Accelerator 480 mm 399 mm 375 mm 193 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 33 Appendix G of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN65 and DN80, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, with Model ACC-1 Accelerator 776 mm 422 mm 367 mm 185 mm I. Normal Conditions III.
  • Page 34 Appendix H of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN100, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, with Model ACC-1 Accelerator 790 mm 395 mm 376 mm 185 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 35 Appendix I of TFP1090 (07/2020) Summary Instructions (If problems occur, consult full document) DN150, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, with Model ACC-1 Accelerator 824 mm 399 mm 346 mm 191 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 36 Appendix J of TFP1090 (07/2020) Summary Instructions (If problems occur, consult full document) DN65 and DN80, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, with Model ACC-1 Accelerator 776 mm DN65 = 416 mm DN80 = 396 mm...
  • Page 37 Appendix K of TFP1090 (07/2020) Summary Instructions (If problems occur, consult full document) DN100, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, with Model ACC-1 Accelerator 790 mm 407 mm 376 mm 193 mm I. Normal Conditions III. Removing System From Service Step 7.
  • Page 38 Appendix L of TFP1090 (07/2020) Summary Instructions (if problems occur, consult full document) DN150, Model DPV-1 Dry Pipe Valve with Standard Alarm Test Valve, with Model ACC-1 Accelerator 824 mm 399 mm 375 mm 193 mm I. Normal Conditions III. Removing System From Service Step 7.

This manual is also suitable for:

Acc-1Dn100Dn150