UPS5000-A-400 kVA
User Manual (60 kVA, PF=0.9)
Number
3
The parameters that have been introduced in the LCD section are not described in the WebUI
section.
The information displayed in Active Alarms and Real-time Data is the same as that on the
LCD, so the information is not described in the WebUI section.

4.2.2.1 Parameter Settings

Figure 4-45 Parameter Settings
System Settings
Item
High ambient
temperature
alarm threshold
(° C)
Low ambient
temperature
alarm threshold
(° C)
EPO detection
D.G. ECO
Bypass Supply
Issue 05 (2019-12-24)
Area
Function
Information
Displays system monitoring information.
area
Description
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When EPO detection is changed
from Disable to Enable, check
that the EPO cable is connected
correctly.
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
55
40–60
–10
–20 to 0
Disable
Disable, Enable
Enable
Disable, Enable